PRODUCT CATEGORY

Dräger Flame 1500 (IR3)

​The Dräger Flame 1500 flame detector uses its triple IR sensor to detect hydrocarbon fires even at great distances. It provides excellent false alarm immunity as approved by FM while maintaining a response time of under 4 seconds.

 


Technical Data

Key Facts

Field of view
Horizontal 90°; Vertical 90°
Response time
Typically 4 seconds
Cable entry
Dual M25 or ¾''NPT
Detection Technology
IR3
Flameproof
Increased Safety
SIL
✓ (SIL 2)
4-20 mA
HART®
RS-485
Relay

Fuel ft / m

n-Heptane / Gasoline
200 / 60
Diesel Fuel / JP5 / Kerosene
165 / 50
Ethanol 95 %
136 / 42
Methanol
136 / 42
IPA (Isopropyl Alcohol)
 
Hydrogen
 
Methane
165 / 50
LPG
 
Polypropylene Pellets
 
Ammonia
 
Silane
 
Office Paper
 

Technical Data

Power Supply
24 V DC
Temperature (operation)
-76°F - 185°F
Humidity
0 to 100 % r.h., non-condensing
Dimensions (H × W × D)
0.72x0.33 ft
Weight
13.23 lb
Housing Material
Aluminium or stainless steel, powder-coated
Degree of protection (IP class)
IP66

Approvals

ATEX
IECEx
UL
CSA
CE marking
GOST (EAC)
Performance approval
Shipping approval (DNV & MED)